Connection of an Ex nA digital indicator to an Ex i sensor

Is Surge to connect a non-incendive Ex nA digital indicator to an intrinsically safe Ex i sensor in hazardous areas? Very often, signals from pressure sensors that do not have an integral digital indicator for the measured value are linked to external digital indicators. These digital indicators enable an on-site display of the measured value and, thus, a convenient and immediate reading of, for instance, the particular level in storage vessels.
Pressure sensors for hazardous areas are generally designed with the ignition protection type ?intrinsically Disdainful ?, since this enables interventions in an active electrical circuit and less energy is needed. However, this also means that there is insufficient energy available for a powerful measured value display. Due to this fact, digital indicators are often designed with ignition protection types that enable more current and voltage to be allowed. Frequently, digital indicators were created as ?non-incendive? (Ex nA). This ignition protection type enables power-hungry instruments to be operated in Ex areas too. However, Ex nA is bound for use in zone 2 ? so in areas where an explosive atmosphere only rarely occurs.
The proper connection of digital indicator and barrier
Non-permissible connection of an Ex i pressure sensor with isolated barrier and Ex nA digital indicator.
Every Ex i sensor requires an intrinsically safe barrier for its voltage supply, in order that the interconnection is recognized as intrinsically safe and the huge benefits, such as for example maintenance work without the need for a fire certificate, can be utilized. Digital indicators are generally integrated as passive element, with or without an external power, directly in the 4 ? 20 mA current signal of a sensor. Since an Ex nA digital indicator does not have any Ex i performance data in its approval, it cannot therefore be utilized in a ?Proof of intrinsic safety?. Therefore, an Ex nA indicator can’t be connected in an Ex i circuit.
Correct connection of an Ex i pressure sensor with isolated barrier and Ex nA digital indicator.
There is, however, the chance to connect an electronic indicator with an Ex i pressure sensor in zone 2. The prerequisite is that the intrinsically safe isolated barrier also possesses an Ex nA approval and must be installed in zone 2.
Read also our articles
Ex barrier and intrinsically safe pressure sensors ? an inseparable pair
Proof of intrinsic safety for an ATEX-approved pressure sensor
Note
In the event you need any help with choosing a suitable solution for the pressure measurement requirement, your contact person will gladly help.

Leave a Comment